Z787

Z787

Log in voor B2B prijs
Ga direct naar de productinformatie
Z787

Z787

Log in voor B2B prijs
  • HOCHIKI
  • Addressable ESP
  • ATEX, EN54
  • Dual Channel

Z787 is a dual-channel intrinsic safety interface module designed to limit the energy transferred from the safe area (sensing loop) to devices located in potentially explosive areas (Zones 0, 1 or 2). Its purpose is to prevent sparks or overheating that could cause a fire, ensuring the integrity of the Hochiki ESP system in critical environments.

This component is critical for compliance with the RIPCI in areas at risk of explosive atmospheres (ATEX), serving as the safety interface between the safe area and the classified area.

  • Certifications: ATEX, EN54
  • ESP Addressable Protocol
  • 2 zones
  • Ultra-Compact Design
  • Dual Channel
  • Integrated Earth

Specifications

Operating Voltage (V) 26,5 V DC
Breakdown Voltage (Uo) 28 V DC
End Resistance (Ro) 300 Ω (Minimum)
Short-Circuit Current (Io) 93 mA
Configuration Dual channel (Positive/Return)
Mounting DIN rail (35mm) with built-in ground connection
Operating Temperature -20°C to +60°C
Dimensions (Body) 12,5 mm (W) x 115 mm (H) x 110 mm (D)
Approximate Weight 150 g
Mounting Type Standard DIN rail of 35 mm (EN 50022)
Housing Material High-temperature-resistant reinforced polycarbonate

In the box

  • 1 x Zener barrier Z787: Dual-channel intrinsically safe module.
  • 1 x Safety and Installation Data Sheet
  • Certification Labeling
  • Grounding clip