BX7B-63N-16A-2P

BX7B-63N-16A-2P

Log in voor B2B prijs
Ga direct naar de productinformatie
BX7B-63N-16A-2P

BX7B-63N-16A-2P

Log in voor B2B prijs
  • Magnetothermic Overvoltage Arrester
  • Nominal current 16A
  • 2 poles (single-phase installations)
  • Type C curve
  • For DIN rail

The BX7B series of circuit breakers is designed to protect low voltage electrical installations against overloads and short circuits. Conforms to the international IEC/EN 60898-1, standard, ensuring widely recognized safety and performance standards in residential, commercial and light industrial applications.

Among its advantages are versatility and compatibility: available in two current ratings and in 2 or 4 pole versions, making them useful in both single-phase and three-phase circuits. Simple installation on standard DIN rail with connections from above or below and good mechanical and thermal support for typical indoor environmental conditions.

The most common scenarios of use are electrical distribution panels in homes, offices, commercial premises and light industrial installations.

  • Magnetothermic Overvoltage Arrester
  • Nominal current 16A
  • 2 poles (single-phase installations)
  • Type C curve
  • For residential, commercial and industrial installations
  • DIN-rail installation
  • IP20
  • Complies with IEC/EN standard 60898-1

Specifications

Range Magnetothermic Overvoltage Arrester
Mounting DIN Rail 35mm (EN 60175))
Terminal type Cable / Busbar (pin-type busbar)
Connection Upper / lower
Upper connection section 25mm2 AWG 18/3
Lower connection section 25mm2 AWG 18/3
Torque 2Nm
Recommended conductor cross-section 2.5mm2 (Nominal current of 13-20A))
Dimensions 35.6 (W) x 81.4 (H) x 79.0 (D) mm

ELECTRICAL CHARACTERISTICS

Rated input current 16A
Number of poles 2P (Single phase)
Nominal voltage 240V
Insulation voltage 500V
Nominal frequency 50/60Hz
Rated jump capacity 6000A
Peak voltage 6000V
Dielectric test voltage at industrial frequency (1 min) 2kV
Type of curve C
Pollution degree 2

MECHANICAL CHARACTERISTICS

Electrical life 6000 operations
Mechanical life 20000 cycles
Degree of protection IP20
Reference temperature 30ºC
Operating temperature -5 - 40ºC
Storing temperature -25 - 70ºC

In the box

  • Magnetothermic Overvoltage Arrester